Skip to main content

🧭 Choose the hosting mode

Each Fuzz site has a hosting mode: Edge (controller installed on the site), Hybrid (controller in the cloud, small gateway on the site) or Cloud (nothing on the site). The choice is made before commissioning, because it determines the hardware to order, the network to plan and how to connect the charge points. This page helps you choose. The detailed operation of each mode is explained in The controller and the hosting modes (Edge, Hybrid, Cloud).


❓ The three questions to ask​

  1. Are there Modbus assets to read or control (meter, photovoltaic inverter, battery, fridge, Modbus charge point)?
    • No, only OCPP charge points (and possibly MQTT assets): all three modes are possible.
    • Yes: Edge or Hybrid. Cloud mode does not handle Modbus.
  2. Must the site keep working when Internet is cut? (protection of a tightly sized connection, guaranteed charging of service vehicles, isolated site)
    • Yes: Edge. In Hybrid and Cloud, nothing works without Internet: neither control nor charging controlled by Fuzz.
  3. What network and Internet access does the site offer?
    • A local network with reliable Internet access, where a controller can be plugged in: Edge (or Hybrid).
    • No usable local network, but Modbus assets to read: Hybrid, with the gateway connected to the assets and Internet access through its 4G modem.
    • Charge points that each have their own connection (4G or site network) and nothing else: Cloud.

πŸ“‹ Decision table​

SituationRecommended modeWhy
Company car park with charge points, main meter, photovoltaic or battery, IT network on siteEdgeEverything is controlled on site, works without Internet, local OCPP URL
Industrial site where the connection is tightly sized and where an overload would trip the main circuit breakerEdgeOverload protection does not depend on Internet
Site with Modbus assets but no possibility of installing a controller on the customer's network (strict IT policy, no network)HybridThe gateway relays Modbus and can use its 4G; the charge points go through Internet
A few isolated charge points, each with a SIM card, with no meter or other assetCloudNothing to install: the charge points connect directly to the Fuzz cloud
Charge points connected through Internet at a customer who accepts no third-party equipment on their networkCloudNo Fuzz hardware on the site
Site with unstable or frequently cut InternetEdgeOnly mode that keeps working offline

Example: the site Nordhem Hognoul has a main meter, a photovoltaic roof and a battery in Modbus TCP, four charging connectors and an IT network in the building: it is in Edge.


🧰 What to plan for each mode​

EdgeHybridCloud
Fuzz hardware on siteOne Fuzz controller (DIN rail, 9-36 V DC or 12-24 V AC power supply)One Fuzz gateway (Ethernet, RS485, 4G modem)None
NetworkOne network socket, a fixed IP address as soon as there are OCPP charge points on the local network, outbound Internet accessOutbound Internet access (Ethernet or 4G); a link to the Modbus assets (local network or RS485)Internet access for each charge point
Charge point connectionPrivate OCPP URL on the local network, or public URL if the site is exposed on the InternetPublic OCPP URL (wss://ocpp.fuzz.energy/...)Public OCPP URL
Modbus assetsConnected to the local network (Modbus TCP) or to the controller's RS485 port (Modbus RTU)Connected to the gateway's local network or to its RS485 portNot supported
Without InternetThe site keeps workingNothing worksNothing works
Controller restart from the ConsoleYesNoNo

πŸ‘‰ See: IT network, Physical installation and The gateway of a Hybrid site


πŸ”„ Choose in the Console and change later​

The mode is chosen when the site is created, in General attributes > Hosting mode (default value: Edge). The Fuzz Controller's serial number list then only offers the free controllers of that mode: check with Fuzz, before commissioning, that you have a controller of the right mode.

Changing the mode of an existing site is not a common operation: its controller also has to be changed or converted, and the charge points often have to receive a new OCPP URL. This change is made by Fuzz: contact support@fuzz.energy.