π³ Electrical topology survey
To configure a site in Fuzz, you must reproduce its electrical diagram in the Console (the topology) and know the communication data of each asset. This page explains what to survey on site or on the plans, and in what form, before commissioning. To understand why this information matters, see Assets and electrical topology.
πΊοΈ 1. Start from the single line diagramβ
Ask for the up-to-date single line diagram of the installation. It must show:
- the grid connection point and its maximum power (kW), or the rating of the head circuit breaker;
- the main low voltage switchboard and its rating per phase (A);
- each sub-switchboard that supplies charge points or assets that Fuzz must control or measure, with its rating and the switchboard that supplies it;
- the busbars and circuit breakers that limit a group of charge points;
- the power and rating of each charge point, of the photovoltaic installation and of the battery;
- the existing meters and what they measure.
Then translate it into a tree, from the grid to the assets. Example for Nordhem Hognoul:
Grid : 100 kW connection
βββ Main low voltage switchboard : 160 A, meter "Compteur principal" (main meter)
βββ Tableau parking (parking switchboard) : 125 A
β βββ Borne P1 (charge point P1, 2 connectors of 32 A, three-phase)
β βββ Borne P2 (charge point P2, 2 connectors of 32 A, three-phase)
βββ Toiture photovoltaΓ―que (rooftop PV) : 80 A
βββ Batterie de stockage (storage battery) : 50 A, 100 kWh
A switchboard that supplies nothing Fuzz knows about does not need to be described. However, a switchboard that limits a group of charge points (for example a 125 A parking switchboard) must be, even if it has no meter.
β‘ 2. Switchboards and metersβ
For each switchboard to describe, note:
| Information | Example | Console field |
|---|---|---|
| Name | Tableau parking | Switchboard name |
| Switchboard that supplies it | Main low voltage switchboard | Position in the topology |
| Rating per phase | 125 A | Maximum current (A) |
| Meter that measures it, if any | β | Meter |
Fuzz applies a margin (Correction factor, 95% by default): it controls a 125 A switchboard at 118.75 A at most. Enter the real rating; the margin is set afterwards in the Console.
Main meter. A meter on the main switchboard lets Fuzz see the whole building's consumption and the photovoltaic injection. It is not mandatory, but without it charging on solar surplus is not possible and the limits must be reduced to the share reserved for charging. See Smart charging without a main meter.
π 3. The information for each assetβ
For each asset (charge point, meter, inverter, battery, fridge, other Modbus asset), note:
| Information | Example |
|---|---|
| Name in Fuzz | Borne P1 - Connecteur 1 |
| Type | Charge point, Meter, Photovoltaic, Battery, Fridge, Generic modbus |
| Brand and model | Alfen S-Line, Phoenix Contact EEM-MA371, Huawei SmartLogger |
| Switchboard that supplies it | Tableau parking |
| Maximum current per phase | 32 / 32 / 32 A |
| Number of phases | 3 (or 1 for a single-phase charge point) |
| Phase wiring order (phase mapping) | L1/L2/L3, or L2/L3/L1 if the phases have been rotated |
| Communication protocol | OCPP, Modbus TCP, Modbus RTU, MQTT |
Check that each model appears in Compatible hardware: the model chosen in the Console (Model) decides which measurements Fuzz can read.
π 4. Survey the phase order (phase mapping)β
Fuzz calculates each phase separately. It must know which grid phase each phase of an asset is wired to.
- Direct wiring: L1 of the asset on L1 of the grid, L2 on L2, L3 on L3. Note
L1/L2/L3. - Rotation: to balance a switchboard, the electrician often shifts the phases from one charge point to the next. Note the real order. For example
L3/L1/L2means:- L1 of the asset β L3 of the grid;
- L2 of the asset β L1 of the grid;
- L3 of the asset β L2 of the grid.
- Single-phase charge point: note the grid phase it is wired to (for example
L2).
A wrong phase mapping can let a phase of a switchboard overload while Fuzz believes the load is balanced. Take the time to survey it at the switchboard.
π See: Settings common to all assets
π 5. Communication dataβ
Depending on each asset's protocol, note the data that lets the controller reach it.
Modbus TCP assetsβ
| Information | Default value in the Console |
|---|---|
| IP address of the asset (fixed) | 192.168.0.1 |
| Modbus port | 502 |
| Unit ID (the asset's Modbus identifier) | To be found in the asset's configuration |
Several assets behind the same Modbus gateway (for example a SmartLogger) share the IP address and are told apart by their Unit ID.
Modbus RTU (RS485) assetsβ
| Information | Remark |
|---|---|
| Serial port used | The RS485 port of the controller (or of the Hybrid gateway), or a USB adapter |
| Unit ID | Unique on the bus |
| Baud rate (speed) | 9600, 19200 (default), 38400 or 115200 |
| Parity, Data bits, Stop bits | Identical for all assets on the same bus |
Also note the bus wiring (order of the assets, end-of-line resistor). See Modbus assets (TCP and RTU).
OCPP charge pointsβ
| Information | Remark |
|---|---|
| Serial number of each charge point (station) | To name it and find it again; some charge points require it in their OCPP URL |
| Number of connectors | One Fuzz charge point per connector |
| Support for OCPP 1.6J and OCPP smart charging | Essential for Fuzz to limit the current |
| Access to the charge point configuration | Manufacturer's app or web interface, installer credentials provided by the manufacturer |
| Authorization mode | Plug & Charge, Local, CPO or Local then CPO. See Charging authorization |
| CPO, if any | CPO URL and the charge point's identifier at the CPO (CPO Station ID) |
| EMI3 identifier (Belgium, Energy Units reports) | EMI3 Identifier |
π See: OCPP configuration of charge points
Assets with a web interfaceβ
Many assets have a configuration page reachable over the local network, which the Console can open remotely (Open Secure Tunnel button). Note:
- the local IP address (fixed);
- the protocol: HTTP or HTTPS;
- the port, if it differs from 80 (HTTP) or 443 (HTTPS).
π See: Open the web interface of an asset remotely
π 6. Example survey sheetβ
Sheet for the Nordhem Hognoul site, as it can be prepared before commissioning:
| Name | Type | Supplied by | Max current | Phases | Protocol and address | Remark |
|---|---|---|---|---|---|---|
| Grid | Grid | β | 100 kW | β | β | Connection power |
| Main low voltage switchboard | Switchboard | Grid | 160 A | β | β | Meter: Compteur principal |
| Compteur principal | Meter | Main low voltage switchboard | 160 A | L1/L2/L3 | Modbus TCP, fixed IP, port 502, Unit ID 1 | |
| Tableau parking | Switchboard | Main low voltage switchboard | 125 A | β | β | No meter |
| Borne P1 - Connecteur 1 and 2 | Charge point | Tableau parking | 32 A | 3, L1/L2/L3 | OCPP, station Borne P1 | Authorizer Plug & Charge |
| Borne P2 - Connecteur 1 and 2 | Charge point | Tableau parking | 32 A | 3, L1/L2/L3 | OCPP, station Borne P2 | Authorizer Plug & Charge |
| Toiture photovoltaΓ―que | Photovoltaic | Main low voltage switchboard | 80 A | L1/L2/L3 | Modbus TCP, fixed IP, port 502, Unit ID 1 | |
| Batterie de stockage | Battery | Main low voltage switchboard | 50 A charge / 50 A discharge | L1/L2/L3 | Modbus TCP, fixed IP, port 502, Unit ID 1 | 100 kWh |
π Next step: Commissioning a site, step by step