π Controller network connection
The Fuzz controller of an Edge site needs two things on the site network: outbound Internet access, to stay in contact with the Fuzz Console, and local access to the assets (OCPP charge points, Modbus TCP assets, web interfaces). This page explains how to connect it, which IP address to give it and how to test the connection. The full list of flows to allow, for the customer's IT department, is in IT network.
π The controller's two Ethernet portsβ
| Port | Technical name | Role | Address |
|---|---|---|---|
| Upper port (1 Gbit/s) | eth0 | Main port: Internet, charge points, Modbus TCP assets, installer menu from the network | DHCP by default, or fixed address |
| Lower port (10/100 Mbit/s) | eth1 | Service port: direct connection of a PC | Always 169.254.254.1 |
Connect the site network to the upper port. The lower port never carries the site's traffic: it stays free, or is used occasionally by a troubleshooting PC.
The MAC address of the upper port (marked MAC0 on the label on the left side of the controller and on the box) is used for two things: it is the controller's serial number in the Console (Fuzz Controller's serial number field), and it is the identifier to give the network administrator for a DHCP reservation.
π Give the controller a fixed IP addressβ
By default, the main port receives its address from the site's DHCP server. This address can change after a restart or a lease renewal.
A fixed address is mandatory as soon as the site has OCPP charge points connected locally: each charge point connects to the controller at an address written in its configuration (the private OCPP URL, for example ws://192.168.1.10:8080/ocpp16/t1d1vauf/yp6u00td). If the controller's address changes, all the charge points lose their connection. Without a local OCPP charge point, the address can stay dynamic.
Two methods:
- DHCP reservation (recommended): the network administrator reserves an address for the controller's MAC0 MAC address. Nothing needs to be done on the controller.
- Fixed address on the controller: from the installer menu, entry 1. Network configuration, switch the IPv4 profile to Manual and enter the address with its prefix (
192.168.1.10/24), the gateway (192.168.1.1) and the DNS servers. The values are provided by the customer's network administrator. Fuzz support can also make this setting remotely if you send them the address, mask, gateway and DNS.
The chosen address must not be used by another device. Once the address is fixed, the private OCPP URL shown in the Console on each charge point's page uses the new address (see OCPP configuration of charge points).
π§° Connect to the service port (169.254.254.1)β
The lower port (eth1) always has the address 169.254.254.1, even with no cable plugged in. It is used when the main port's address is not known (DHCP without access to the lease list) and the Console does not give access to the controller (controller not yet online).
- Plug a PC directly into the controller's lower port with an Ethernet cable.
- Give the PC a fixed address:
169.254.254.2, mask255.255.255.0(no gateway). - Open a browser at
http://169.254.254.1:1080: the web terminal shows the installer menu. - Log in, then check the main port's address (2. Network diagnostics > View current configuration) or configure a fixed address (1. Network configuration).
The service port gives no Internet access and does not replace the main port. Unplugging or plugging a cable on this port does not interrupt the controller's connection to Fuzz.
βοΈ Internet access the controller needsβ
The controller opens no inbound port on the site network: it opens outbound connections to Fuzz itself. The site firewall must allow, at a minimum:
| Outbound flow | Use |
|---|---|
| DNS (UDP/TCP 53) | Resolving the names of the Fuzz services |
| HTTPS (TCP 443) to the Fuzz services and the cloud services listed in IT network | Onboarding, configuration, measurements |
| TCP 22 to the Fuzz Secure Link server | Secure connection with the Console (remote access, installer console, asset web interfaces) |
| NTP (UDP 123) | Accurate time, essential for secure connections |
The exact list of addresses and ports, to pass on to the customer's IT department, is maintained on a single page: IT network. A firewall or proxy that intercepts HTTPS traffic can prevent onboarding: the Network diagnostics > Diagnostics entry of the installer menu reports it.
If the network requires an internal time server, configure it with entry 6. Set NTP server of the installer menu.
π Local traffic between the controller and the assetsβ
On the site network, the controller exchanges with the assets:
| Exchange | Who connects to whom | Port | Fixed address needed |
|---|---|---|---|
| Charge points over OCPP 1.6 JSON | The charge point connects to the controller | 8080 on the controller (WebSocket ws://) | For the controller (not for the charge points) |
| Modbus TCP assets (meters, inverters, batteries) | The controller connects to the asset | 502 usually, on the asset | For each asset |
| Asset web interfaces | The controller relays the web page to the Console | 80 or 443 usually, on the asset | For each asset |
| MQTT assets to the local broker | The asset publishes to the controller | 1883 on the controller | For the controller |
The controller and the assets must be on the same network, or on networks routed to each other without filtering of these ports. See Modbus assets, OCPP configuration of charge points and MQTT devices.
π Test the connection with Network diagnosticsβ
In the installer menu, entry 2. Network diagnostics > Diagnostics shows the main port's configuration, then a connectivity check. Each line starts with [OK] or [FAIL]:
| Line displayed | What is tested | If [FAIL] |
|---|---|---|
eth0 address: β¦ / eth0 has no IPv4 address | The main port has an address | Check the cable (upper port), DHCP or the fixed address |
NetworkManager reports eth0 as connected | The Ethernet link is active | Check the cable and the switch |
IP connectivity to 8.8.8.8 | Outbound to the Internet (ping) | Check the gateway; some firewalls only block ping, without affecting Fuzz |
DNS resolution for auth.fuzz.energy | DNS resolution | Check the DNS servers |
HTTPS access to auth.fuzz.energy | HTTPS access to the Fuzz services | Ask for outbound port 443 to be opened; message Hint: DNS works but HTTPS fails; check the client proxy or firewall. |
TCP port 22 on evproxy.fuzz.energy | Access to the Fuzz Secure Link server | Ask for outbound port 22 to be opened |
The check ends with Connectivity check passed. when everything is correct, or Connectivity check found N problem(s). The Test remote connectivity entry tests a specific TCP port to an address of your choice, for example 192.168.1.50 port 502 for a Modbus meter.
π οΈ Common network problemsβ
| Symptom | Likely cause | Solution |
|---|---|---|
| OCPP charge points disconnect after a restart of the controller or the router | The controller's DHCP address has changed | Fix the address (DHCP reservation or fixed address), then check the charge points' OCPP URL |
The installer menu is not reachable at http://<ip>:1080 | Wrong address, PC on another network | Use the service port 169.254.254.1 |
[FAIL] HTTPS access to auth.fuzz.energy | Outbound port 443 closed or HTTPS proxy | Have the flows in IT network opened |
[FAIL] TCP port 22 on evproxy.fuzz.energy | Outbound port 22 closed | Have outbound port 22 to the Fuzz server opened |
| A Modbus TCP asset stays offline | Asset address unknown or filtered | Test with Test remote connectivity (address and port 502) |