Skip to main content

πŸ“‘ The gateway of a Hybrid site

On a site with the Hybrid hosting mode, the Fuzz controller does not run on site: it runs in the Fuzz cloud. On site, a small box, the Fuzz gateway, relays traffic between this controller and the assets on the local network. This page explains what the gateway does, how to bring it online, its installer menu and its limits. To choose between Edge, Hybrid and Cloud, see Choose the hosting mode.

🧩 What the gateway does, and what it does not do​

The gateway…Detail
relays Modbus TCPThe cloud controller polls the meters, inverters and batteries of the local network through it
relays Modbus RTUIt has an RS485 port: Modbus RTU assets are wired to this bus
relays the web interfaces of the assetsThe Open the web interface of an asset remotely feature goes through it
connects over Ethernet or 4G4G can be its only access to the Internet
does not control anything itselfSmart charging, alerts and measurement collection are calculated by the controller in the cloud
does not receive the OCPP charge pointsCharge points connect directly to the Fuzz public OCPP URL, over the Internet (see OCPP configuration of charge points)
does not host an MQTT brokerThe local MQTT broker exists only in Edge; in Hybrid, use the Fuzz cloud MQTT broker or another broker (see MQTT devices)

The hardware is an industrial EDATEC ED-IPC1100 box (Raspberry Pi CM0, 512 MB of RAM, 8 GB eMMC, one 100 Mbit/s Ethernet port, one RS485 port, 4G modem). To obtain a gateway, contact Fuzz.


🌍 A Hybrid site needs Internet at all times​

The controller of a Hybrid site is in the cloud. Without Internet on site, nothing works: no more control of the charge points or assets, no more OCPP connection of the charge points, no more measurements. Only an Edge site keeps controlling the site locally during an Internet outage.

Other differences with an Edge site, visible in the Console:

  • there is no private OCPP URL on the charge points page, only the public OCPP URL;
  • the site's Admin menu has no Reboot controller action: the cloud controller is shared with other sites and is not restarted from a site;
  • the Installer SSH console (site Admin > Actions menu) opens the gateway's installer menu;
  • the site parameters have a Firewall step specific to the Hybrid mode;
  • the logs of the gateway itself are not sent to the Console; the site logs (Monitoring > Controller > Logs) are those of the cloud controller.

The hosting mode of a site cannot be changed in the Console: to switch a site from Edge to Hybrid (or the reverse), contact Fuzz.


πŸš€ Install the gateway and bring it online​

Bringing the gateway online follows the same steps as for an Edge controller (see Putting the controller online (onboarding)):

  1. Connect the gateway to the site network over Ethernet, or insert a SIM card for 4G, then power it on.
  2. In the Console, open the site, then Configuration > Site Parameters, step General attributes: Hosting mode must be Hybrid, and Fuzz Controller's serial number must be the gateway's serial number (the MAC address of its Ethernet port, in lowercase). Only serial numbers registered in Hybrid mode are offered.
  3. The gateway registers itself with Fuzz and retries every 60 seconds if it fails.
  4. Follow the progress in the installer menu, entry 5. Onboarding status, or in your company's Onboarding logs (Monitoring > Controller > Logs).

Messages specific to the gateway: Start Fuzz gateway onboarding at the start, The Fuzz gateway has been successfully onboarded at the end. The message This device runs the Fuzz gateway image but its controller is not a Gateway controller (hosting mode: Local) means that this serial number is registered at Fuzz as an Edge controller and not as a gateway: contact Fuzz support. The message SSH keys already exchanged for this controller: reset them in Fuzz Console is handled as for an Edge controller: ask Fuzz support to reset the keys.

Access to the installer menu is the same as for the Edge controller: web terminal on port 1080, installer account, password = Ethernet MAC address in lowercase with the colons (see Installer menu).


πŸ§‘β€πŸ”§ Gateway installer menu​

The gateway menu is titled Fuzz gateway installer menu. The common entries work as on the Edge controller (Installer menu); three entries are specific to it.

No.EntryPurpose
1Network configurationIP address of the Ethernet port (DHCP or fixed)
2Network diagnosticsConfiguration and connectivity tests; also shows the 4G status
3Ethernet role (WAN or LAN only)WAN + LAN: Internet goes through Ethernet when it is available. LAN only (Internet through 4G): Ethernet is used only for the site's assets, Internet goes through 4G
44GSubmenu: Status, Set APN, Set SIM PIN, Restart the 4G connection, Reset the 4G module
5Onboarding statusOnboarding follow-up
6Restart onboarding and follow logsRestart a stuck onboarding
7Reverse SSH statusStatus of the Fuzz Secure Link connection
8Gateway statusVersions, site configuration applied by Fuzz, status of the relay and of the RS485 buses
9Set NTP serverTime server
10LogoutClose the session

4G settings:

  • Set APN: leave empty for an automatic APN; otherwise enter the operator's APN, then the APN user and password if there are any.
  • Set SIM PIN: PIN code of the SIM card (4 to 8 digits), empty if the card has no PIN. The menu displays SIM PIN updated.
  • Status shows the address obtained over 4G, the APN in use ((automatic) by default) and the status of the 4G service.

Gateway status displays Site configuration applied by the cloud: (the site configuration received from Fuzz) and No Modbus RTU bridge configured. when no Modbus RTU asset is declared on the site.


πŸ”§ Declare the assets of a Hybrid site​

Assets are declared in the Console as on an Edge site (see Modbus assets), with three rules specific to the gateway:

RuleConsole message if it is not met
A Modbus TCP asset is identified by a numeric IPv4 address (192.168.1.50), never by a nameAsset …: a Gateway site reaches its Modbus TCP assets by numeric IPv4 address, got …
A Modbus RTU asset uses the port (RS485) /dev/rs485, and all the assets on the same bus have the same speed, data bits, parity and stop bitsAssets … and … share the serial bus /dev/rs485 with different serial settings (baud rate, data bits, parity, stop bits)
The web interface address of an asset is an IPv4 address or a valid host name, never 127.0.0.1Asset …: invalid console host …

After saving, Fuzz sends the gateway the list of addresses to relay; it applies the list as soon as it is online.

Gateway firewall (Firewall step)​

By default, the gateway relays only to the exact addresses and ports of the assets declared on the site (Modbus TCP address and port, web interface address and port) and to its RS485 bus: any other destination is refused. This setting is the Enable IP address protection option (ticked by default) of the Firewall step of the site parameters. Untick it only temporarily, to reach a device not yet declared as an asset. See Gateway firewall.

πŸ› οΈ Common problems on a Hybrid site​

SymptomLikely causeSolution
All assets and all charge points offlineNo Internet on site, or gateway powered offCheck the power supply, the cable or 4G (4G > Status, Network diagnostics)
One Modbus TCP asset offline, the others onlineWrong address or port, gateway firewallCheck the address in the Console, test with Network diagnostics > Test remote connectivity
RS485 assets do not respondWrong serial settings, A/B wiring swappedSee Wiring an RS485 bus
The charge point does not connectPrivate OCPP URL usedIn Hybrid, use the public OCPP URL
4G does not connectIncorrect APN or PIN4G > Set APN and Set SIM PIN, then Restart the 4G connection