Skip to main content

🖧 What are the IT requirements of the Fuzz controller?

The Fuzz controller of an Edge site plugs into the local network of the site. It needs no inbound port from the Internet: it is the one that opens its connections to Fuzz. The full list of addresses, ports and rules to give to the customer's IT department is on the page IT network.

The essentials to ask the IT department​

NeedDetail
Controller IP addressA fixed address on the site network: DHCP reservation on the MAC address, or address configured on the controller with the installer menu
Connection to FuzzOutbound traffic allowed to evproxy.fuzz.energy on port 22 (TCP, Fuzz Secure Link) and to api.fuzz.energy and auth.fuzz.energy on port 443 (HTTPS)
Cloud servicesOutbound traffic allowed to the AWS addresses listed in IT network (ports 443, 8443 and 8883)
DNSA DNS server that resolves Internet names
TimeNTP allowed (UDP 123), or an internal NTP server set in the installer menu
Local networkThe controller reaches the Modbus TCP assets (port 502 by default); charge points reach the controller over OCPP (port 8080); fixed IP addresses for the Modbus assets and for those whose web interface is opened remotely

A stateful firewall handles the return traffic of these outbound connections on its own; a stateless device must allow it explicitly.

What about a Hybrid or Cloud site?​

In both cases, without Internet on the site, nothing works: see What happens if the site loses Internet?.

👉 See: IT network, Controller network connection and Choose the hosting mode